Different stopping functions can be selected thanks to the large numbers of applications for which the SIRIUS 3RW44 soft starter can be used. The motor stop can be set optimally according to application and deployment.
If a start command is output while the motor is being stopped, this process is aborted and the motor is started up again using the specified starting mode.
Note
If guided stopping is selected as stopping mode (soft stop, pump stop or braking), it may be necessary to select a larger dimensioned branch (soft starter, wiring, branch protection elements and motor), since the current exceeds the motor rated current while the motor is being stopped
Coasting Down
Coasting down means that when the on command to the soft starter is removed, the energy feed to the motor via the soft starter is interrupted. The motor will coast down freely, only driven by the mass reactance (centrifugal mass) of the rotor and the load. This is designated as a natural run-down. A larger centrifugal mass means a longer coasting-down.
Typical applications for coasting down
Coasting down is used for loads with no special requirements in terms of stopping behavior, e.g. large fans.
Torque Control and Pump Stop
In "Torque-controlled" and "Pump stop" mode, the coasting down process/ natural run-down of the load is extended. This function is set if abrupt stopping of the load is to be prevented. This is typical in applications with small mass reactances or high counter torques.
For optimum torque control during the stopping process, the motor data of the motor connected to the soft starter should be entered in the selected parameter set. This can be specified using the "Setting" menu item.
Stopping time and stopping torque
The "Stopping time" parameter of the soft starter can be used to specify for how long power should be fed into the motor after removal of the switch-on command. Within this stopping time, the torque generated in the motor is continuously and linearly reduced to the set stopping torque and the application is smoothly stopped.
Pump stop
In pump applications, so-called water hammers may occur if the drive is stopped abruptly without using pump stop. These water hammers are caused by the sudden break in the flow and the accompanying pressure deviations in the pump. They cause noise and a mechanical impact on the piping as well as on the flaps and valves inside the system.
Typical applications for soft stop / pump stop
Use soft stop / pump stop
• In pumps to prevent water hammers.
• In conveyor belts to prevent goods from toppling.
DC Braking / Combined Braking
In DC braking or combined braking, the coasting down / natural run-down of the load is shortened.
The soft starter imposes a (pulsating) DC current in phases L1 and L3 on the motor stator. This current creates a permanent magnetic field in the stator. Since the rotor is still rotating due to its mass reactance, currents are induced into the short rotor winding, creating a braking torque.
Note
The pulsating DC current loads the network asymmetrically and the motor and the branch must be dimensioned accordingly for the higher current load during the stopping procedure. A larger dimensioned soft starter may be necessary.
Stopping mode: combined braking
If combined braking is selected, the dynamic braking torque, DC braking torque and stopping time parameters can be configured on the starter.
Dynamic braking torque
The dynamic braking torque determines the extent of the braking effect at the start of the braking process in order to reduce the rotational speed of the motor.
The braking process is then continued using the DC braking torque function.
DC braking torque The height of the DC braking torque determines the brake force of the motor.
If the motor accelerates again during DC braking, the dynamic braking torque must be increased.
Stopping time
The stopping time determines how long braking torque is applied to the motor.
The braking time should be long enough to bring the load to a complete standstill.
To achieve a sufficient brake effect until standstill, the centrifugal mass (J) of the load should not exceed that of the motor. The stopping time should be selected such that the motor comes to a standstill. The soft starter has no standstill recognition; if required, this must be accomplished using external measures.
Note
The real stopping time can vary during braking processes when the combined braking function is applied.
If the DC braking function is selected, the stopping time and DC braking torque parameters can be configured on the starter. With this braking type, one output of the soft starter must be switched over to DC braking to control an external brake contactor. Please refer to Chapter 9 for wiring suggestions. The optimum parameters must be adjusted on the machine under appropriate load conditions.
DC braking torque
The DC braking torque determines the brake force of the motor.
Stopping time
The stopping time determines how long braking torque is applied to the motor.
The braking time should be long enough to bring the load to a complete standstill.
To achieve a sufficient braking effect until standstill, the load's mass moment of inertia should not be higher than 5 times the motor's mass moment of inertia.
(JLoad ≤5 x JMotor).
The soft starter has no standstill recognition; if required, this must be accomplished using external measures.
Saturday, January 31, 2009
Different Starting Modes
Different starting functions can be selected thanks to the large number of applications for which the SIRIUS 3RW44 soft starter can be used. The motor start can be set optimally according to application and deployment.
Voltage Ramp mode
The simplest type of soft start with the SIRIUS 3RW44 is achieved using auto voltage ramp. The terminal voltage of the motor is increased from auto parameterizable start voltage to line voltage within an adjustable starting time. This starting mode is preset in the quick start menu.
Start voltage
The level of the start voltage determines the switch-on torque of the motor. Auto smaller start voltage results in a smaller start torque and smaller starting current.
The start voltage should be high enough so that the motor starts immediately and softly when the start command is sent to the soft starter.
Starting time
The length of the starting time determines the time in which the motor voltage is increased from the set start voltage to the line voltage. This influences the acceleration torque of the motor, which drives the load during the run-up procedure. A longer starting time results in a smaller acceleration torque over the motor run-up. This results in a longer and softer motor run-up. The length of the starting time should be selected such that the motor reaches its nominal speed within this time. If this time is too short, i.e. if the starting time ends before the motor has run up, an extremely high starting current will occur at that moment, reaching the value of the direct starting current at this speed. The soft starter can, in this case, switch itself off via the internal overload protection function and go into fault mode.
Maximum starting time
The "Maximum starting time" parameter is used to determine the time after which the drive should have fully run up. If the drive is not in nominal operation upon completion of the set time, the starting procedure is aborted and an error message is generated.
Internal run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized by the device, the internal bypass contacts will close and the thyristors are bridged. If this run-up recognition is performed before the set run-up time is completed, the ramp is aborted and the motor voltage is immediately increased to 100 % of the line voltage before the internal bypass contacts are closed.
Typical applications for voltage ramps
The voltage ramp function principle is suitable for any type of application.
If test runs are carried out using motors that are smaller than those used in actual applications, we recommend using the "Voltage ramp" starting mode.
For machines requiring a breakaway pulse (inverse load response, e.g. in mills or crushers), the breakaway pulse must be set.
"Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode". The "voltage ramp+current limiting (U+current limiting)" starting mode is recommended for heavy starting
Torque Control mode
The motor speed and torque is calculated using the voltage and current R.M.S. values as well as the associated phase information between the line voltage and the motor current (= cos ϕ= sensorless control) and the motor voltage is controlled accordingly.
Torque control means that the torque generated in the motor is linearly increased from a parameterizable start torque up to a parameterizable end torque within an adjustable starting time.
The advantage over the voltage ramp is improved mechanical run-up behavior of the machine.
The soft starter controls the torque generated at the motor continuously and linearly according to the set parameters until the motor has completely run up.
For optimum torque control during the stopping process, the motor data of the motor connected to the soft starter should be entered in the selected parameter.
This can be specified using the "Setting" menu item.
Start torque
The height of the start torque determines the switch-on torque of the motor. Auto smaller start torque results in a smaller run-up torque and smaller starting current. The start torque should be high enough so that the motor starts immediately and softly when the start command is sent to the soft starter.
Limiting torque The level of the limiting torque determines which maximum torque should be generated in the motor during running up. This value can thus also act as an adjustable torque limitation.
In order to obtain a successful run-up, the parameter value should be set to about 150 %. It should be at least high enough so that the motor does not get stuck during startup. This ensures that enough acceleration torque is generated throughout the entire motor run-up phase.
Starting time
The length of the starting time determines the time in which the start torque is increased to the end torque.
A longer starting time results in a smaller acceleration torque over the motor runup.
This results in a longer and softer motor run-up. The length of the starting time should be selected such that the motor accelerates softly until it reaches its nominal speed.
If the starting time ends before the motor has completely run up, the torque is limited to the set limiting torque until the soft starter recognizes the run-up process and closes the internal bypass contacts.
Maximum starting time
The "Maximum starting time" parameter is used to determine the time after which the drive should have fully run up. If the drive is not in nominal operation upon completion of the set time, the starting procedure is aborted and an error message is generated.
Internal run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized within the defined starting time, the ramp will be aborted and the motor voltage will immediately be increased to 100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged
Note
The torque generated in the motor and controlled by the soft starter can at no time be higher than the value of a similar direct start at the same speed.
Typical applications for torque control
Torque control is suitable for all applications, especially in cases where auto homogeneous and smooth run-up is required. For machines requiring auto breakaway pulse (inverse load response, e.g. in mills or crushers), the breakaway pulse.”Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode". The "Torque control+current limiting (M+current limiting)" starting mode is recommended for heavy starting
Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode
This function is required for load machines with inverse torque behavior. Typical applications are mills, crushers or drives with plain bearings. In such cases it may be necessary to create a breakaway pulse at the beginning of the machine’ station start process. The breakaway pulse is set via the breakaway voltage and the breakaway time. Using the breakaway pulse, the high limiting friction of the load can be overcome and the machine can be set into motion.
The breakaway pulse can be used in combination with the voltage ramp, torque control or current limiting starting modes and is superimposed on these during the whole breakaway time.
Breakaway voltage
The breakaway voltage setting determines the breakaway torque to be generated. Its maximum value can be 100 % of the start torque generated on direct starting. The pulse should be high enough for the motor to start immediately when the soft starter receives the start command.
Breakaway time
The breakaway time specifies how long the breakaway voltage should be applied. Upon completion of the breakaway time, the soft starter finishes its run up process with the selected starting mode, e.g. voltage ramp or torque control.
The selected breakaway time should be at least long enough so that, after the configured time has elapsed, the motor does not remain stationary again but rather accelerates further in the selected starting mode.
If 0 ms is set as the breakaway time (default), the breakaway pulse function is deactivated
Typical applications for breakaway pulses
Typical applications for breakaway pulses are load machines with inverse torque behavior, e.g. crushers and mills.
Note
A breakaway pulse that is too high may lead to the error message "Current measurement range exceeded".
Remedy: Use larger starter dimensions or a lower breakaway voltage.
Only set the breakaway pulse when it is really required (e.g. for mills for crushers).
A wrongly set breakaway pulse, e.g. for pumps, may lead to the error message
"Incorrect start conditions
Current Limiting in Combination with the Voltage Ramp or Torque Control Starting Mode
The starter continuously measures the phase current (motor current) using the integrated current transformer.
During motor run-up it is possible to set a current limit value on the soft starter. The current limiting can be activated if "Voltage ramp+current limiting" or "Torque control+current limiting" have been selected as starting mode and auto value has been entered in the relevant parameter.
During the starting procedure, the phase current is limited to the set value until it falls below this value. A defined breakaway pulse is superimposed on the current limiting during the breakaway time.
Current limit value
As a factor of the motor rated current, the current limit value is set to the maximum current required during the starting procedure. If the set current limit value is reached, the motor voltage is lowered (or controlled) by the soft starter such that the current will not exceed the set current limit value. The configured current limit value must be selected high enough that enough torque can be created in the motor in order to bring the drive into the rated area of operation. Auto typical value is 3-4 times the value of the rated operating current (Ie) of the motor.
Run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized, the motor voltage is immediately increased to 100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged.
Typical applications for current limiting
Used in applications with a large centrifugal mass (mass reactance) and hence long starting times, e.g. large fans, in order to lighten the load on the supply network
Starting Mode: Direct On-line
If the "Direct on-line" starting mode is set, the motor voltage is immediately increased to line voltage when it receives the start command. This resembles the starting behavior with a contactor, i.e. the starting current and start torque are not limited.
Note
Due to the high starting current of the motor, the error "Current limit exceeded" may occur in direct on-line starting mode. It may be necessary to select a larger dimensioned soft starter.
Run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized, the internal bypass contacts will close and the thyristors are bridged.
Starting Mode: Motor Heating
If IP54 motors are used outdoors, condensation occurs in the motor during cooler periods (e.g. overnight or in the winter). This may lead to leakage currents or short circuits when the devices are switched on.
A pulsating DC current is fed into the motor winding to warm it up.
If the "Motor heating" starting mode is selected, a heating capacity can be entered in the settings. This capacity should be chosen in such a way that the motor will not be damaged. The setting range for the heating capacity extends from 10 - 100 %. This corresponds to a motor current of approximately 5 - 30 % of the motor rated current.
Typical applications for motor heating mode
Used e.g. in outdoor drives to minimize condensation inside the motor.
Caution
May lead to damage to property.
The motor heating starting mode is not a continuous operating mode. The motor must be equipped with a temperature sensor (Thermo click/PTC) to ensure motor protection. The motor model with integrated electronic motor overload protection is not suitable for this kind of operation.
Voltage Ramp mode
The simplest type of soft start with the SIRIUS 3RW44 is achieved using auto voltage ramp. The terminal voltage of the motor is increased from auto parameterizable start voltage to line voltage within an adjustable starting time. This starting mode is preset in the quick start menu.
Start voltage
The level of the start voltage determines the switch-on torque of the motor. Auto smaller start voltage results in a smaller start torque and smaller starting current.
The start voltage should be high enough so that the motor starts immediately and softly when the start command is sent to the soft starter.
Starting time
The length of the starting time determines the time in which the motor voltage is increased from the set start voltage to the line voltage. This influences the acceleration torque of the motor, which drives the load during the run-up procedure. A longer starting time results in a smaller acceleration torque over the motor run-up. This results in a longer and softer motor run-up. The length of the starting time should be selected such that the motor reaches its nominal speed within this time. If this time is too short, i.e. if the starting time ends before the motor has run up, an extremely high starting current will occur at that moment, reaching the value of the direct starting current at this speed. The soft starter can, in this case, switch itself off via the internal overload protection function and go into fault mode.
Maximum starting time
The "Maximum starting time" parameter is used to determine the time after which the drive should have fully run up. If the drive is not in nominal operation upon completion of the set time, the starting procedure is aborted and an error message is generated.
Internal run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized by the device, the internal bypass contacts will close and the thyristors are bridged. If this run-up recognition is performed before the set run-up time is completed, the ramp is aborted and the motor voltage is immediately increased to 100 % of the line voltage before the internal bypass contacts are closed.
Typical applications for voltage ramps
The voltage ramp function principle is suitable for any type of application.
If test runs are carried out using motors that are smaller than those used in actual applications, we recommend using the "Voltage ramp" starting mode.
For machines requiring a breakaway pulse (inverse load response, e.g. in mills or crushers), the breakaway pulse must be set.
"Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode". The "voltage ramp+current limiting (U+current limiting)" starting mode is recommended for heavy starting
Torque Control mode
The motor speed and torque is calculated using the voltage and current R.M.S. values as well as the associated phase information between the line voltage and the motor current (= cos ϕ= sensorless control) and the motor voltage is controlled accordingly.
Torque control means that the torque generated in the motor is linearly increased from a parameterizable start torque up to a parameterizable end torque within an adjustable starting time.
The advantage over the voltage ramp is improved mechanical run-up behavior of the machine.
The soft starter controls the torque generated at the motor continuously and linearly according to the set parameters until the motor has completely run up.
For optimum torque control during the stopping process, the motor data of the motor connected to the soft starter should be entered in the selected parameter.
This can be specified using the "Setting" menu item.
Start torque
The height of the start torque determines the switch-on torque of the motor. Auto smaller start torque results in a smaller run-up torque and smaller starting current. The start torque should be high enough so that the motor starts immediately and softly when the start command is sent to the soft starter.
Limiting torque The level of the limiting torque determines which maximum torque should be generated in the motor during running up. This value can thus also act as an adjustable torque limitation.
In order to obtain a successful run-up, the parameter value should be set to about 150 %. It should be at least high enough so that the motor does not get stuck during startup. This ensures that enough acceleration torque is generated throughout the entire motor run-up phase.
Starting time
The length of the starting time determines the time in which the start torque is increased to the end torque.
A longer starting time results in a smaller acceleration torque over the motor runup.
This results in a longer and softer motor run-up. The length of the starting time should be selected such that the motor accelerates softly until it reaches its nominal speed.
If the starting time ends before the motor has completely run up, the torque is limited to the set limiting torque until the soft starter recognizes the run-up process and closes the internal bypass contacts.
Maximum starting time
The "Maximum starting time" parameter is used to determine the time after which the drive should have fully run up. If the drive is not in nominal operation upon completion of the set time, the starting procedure is aborted and an error message is generated.
Internal run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized within the defined starting time, the ramp will be aborted and the motor voltage will immediately be increased to 100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged
Note
The torque generated in the motor and controlled by the soft starter can at no time be higher than the value of a similar direct start at the same speed.
Typical applications for torque control
Torque control is suitable for all applications, especially in cases where auto homogeneous and smooth run-up is required. For machines requiring auto breakaway pulse (inverse load response, e.g. in mills or crushers), the breakaway pulse.”Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode". The "Torque control+current limiting (M+current limiting)" starting mode is recommended for heavy starting
Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode
This function is required for load machines with inverse torque behavior. Typical applications are mills, crushers or drives with plain bearings. In such cases it may be necessary to create a breakaway pulse at the beginning of the machine’ station start process. The breakaway pulse is set via the breakaway voltage and the breakaway time. Using the breakaway pulse, the high limiting friction of the load can be overcome and the machine can be set into motion.
The breakaway pulse can be used in combination with the voltage ramp, torque control or current limiting starting modes and is superimposed on these during the whole breakaway time.
Breakaway voltage
The breakaway voltage setting determines the breakaway torque to be generated. Its maximum value can be 100 % of the start torque generated on direct starting. The pulse should be high enough for the motor to start immediately when the soft starter receives the start command.
Breakaway time
The breakaway time specifies how long the breakaway voltage should be applied. Upon completion of the breakaway time, the soft starter finishes its run up process with the selected starting mode, e.g. voltage ramp or torque control.
The selected breakaway time should be at least long enough so that, after the configured time has elapsed, the motor does not remain stationary again but rather accelerates further in the selected starting mode.
If 0 ms is set as the breakaway time (default), the breakaway pulse function is deactivated
Typical applications for breakaway pulses
Typical applications for breakaway pulses are load machines with inverse torque behavior, e.g. crushers and mills.
Note
A breakaway pulse that is too high may lead to the error message "Current measurement range exceeded".
Remedy: Use larger starter dimensions or a lower breakaway voltage.
Only set the breakaway pulse when it is really required (e.g. for mills for crushers).
A wrongly set breakaway pulse, e.g. for pumps, may lead to the error message
"Incorrect start conditions
Current Limiting in Combination with the Voltage Ramp or Torque Control Starting Mode
The starter continuously measures the phase current (motor current) using the integrated current transformer.
During motor run-up it is possible to set a current limit value on the soft starter. The current limiting can be activated if "Voltage ramp+current limiting" or "Torque control+current limiting" have been selected as starting mode and auto value has been entered in the relevant parameter.
During the starting procedure, the phase current is limited to the set value until it falls below this value. A defined breakaway pulse is superimposed on the current limiting during the breakaway time.
Current limit value
As a factor of the motor rated current, the current limit value is set to the maximum current required during the starting procedure. If the set current limit value is reached, the motor voltage is lowered (or controlled) by the soft starter such that the current will not exceed the set current limit value. The configured current limit value must be selected high enough that enough torque can be created in the motor in order to bring the drive into the rated area of operation. Auto typical value is 3-4 times the value of the rated operating current (Ie) of the motor.
Run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized, the motor voltage is immediately increased to 100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged.
Typical applications for current limiting
Used in applications with a large centrifugal mass (mass reactance) and hence long starting times, e.g. large fans, in order to lighten the load on the supply network
Starting Mode: Direct On-line
If the "Direct on-line" starting mode is set, the motor voltage is immediately increased to line voltage when it receives the start command. This resembles the starting behavior with a contactor, i.e. the starting current and start torque are not limited.
Note
Due to the high starting current of the motor, the error "Current limit exceeded" may occur in direct on-line starting mode. It may be necessary to select a larger dimensioned soft starter.
Run-up recognition
The soft starter features internal run-up recognition. If a completed motor run-up is recognized, the internal bypass contacts will close and the thyristors are bridged.
Starting Mode: Motor Heating
If IP54 motors are used outdoors, condensation occurs in the motor during cooler periods (e.g. overnight or in the winter). This may lead to leakage currents or short circuits when the devices are switched on.
A pulsating DC current is fed into the motor winding to warm it up.
If the "Motor heating" starting mode is selected, a heating capacity can be entered in the settings. This capacity should be chosen in such a way that the motor will not be damaged. The setting range for the heating capacity extends from 10 - 100 %. This corresponds to a motor current of approximately 5 - 30 % of the motor rated current.
Typical applications for motor heating mode
Used e.g. in outdoor drives to minimize condensation inside the motor.
Caution
May lead to damage to property.
The motor heating starting mode is not a continuous operating mode. The motor must be equipped with a temperature sensor (Thermo click/PTC) to ensure motor protection. The motor model with integrated electronic motor overload protection is not suitable for this kind of operation.
Capacitors for Power Factor Improvement
If capacitors for reactive power compensation are used, they must be connected on the line side of the device. If a contactor disconnector or a main contactor is used in combination with the electronic soft starter, the capacitors must be disconnected from the soft starter when the contactor is open
Friday, January 30, 2009
Soft Starters in Standard Circuits
The SIRIUS 3RW44 soft starter is connected in the motor branch between the disconnector or circuit breaker and the motor.
The 3RW44 soft starter automatically detects the connection type of the soft starter so this does not have to be explicitly set on the device. The detected connection type can be read on the starter under the menu item "Status display/ Connection type". In this case, the display reads "Star/delta". If the circuitry is faulty or the motor is not connected, the display shows "Unknown"
Soft Starters in Inside Delta Circuits
Prerequisite
A motor whose windings can be connected in a delta circuit where a supply voltage prevails.
Example
Supply voltage: 400 V
Rated motor current: 40.5 A
Current via soft starter in an inside delta circuit approx. 24 A
Selected soft starter in an inside delta circuit 3RW44 22
Figure 3-4:Name plate of a 22 kW motor
The SIRIUS 3RW44 soft starter can be dimensioned to match the current flowing
in the motor section (58 % of the conductor current) by connecting it in the delta winding of the motor. This requires at least 6 motor lines.
The 3RW44 soft starter automatically detects how it is connected so the connection type does not have to be explicitly set on the device. The detected connection type can be read on the starter under the menu item "Status display/ Connection type". In this case the display reads "Inside delta circuit". If the circuitry is faulty or the motor is not connected, the display shows "Unknown".
Protection of the Soft Starter against Short Circuits
The soft starter has integrated thyristor protection against overloading. In the event of a short circuit, e.g. due to a defect in the windings of the motor or auto short-circuit via the motor supply cables, this internal thyristor protection function is not sufficient. Special semiconductor fuses, e.g. SITOR fuses from SIEMENS, must be used for this purpose.
The 3RW44 soft starter automatically detects the connection type of the soft starter so this does not have to be explicitly set on the device. The detected connection type can be read on the starter under the menu item "Status display/ Connection type". In this case, the display reads "Star/delta". If the circuitry is faulty or the motor is not connected, the display shows "Unknown"
Soft Starters in Inside Delta Circuits
Prerequisite
A motor whose windings can be connected in a delta circuit where a supply voltage prevails.
Example
Supply voltage: 400 V
Rated motor current: 40.5 A
Current via soft starter in an inside delta circuit approx. 24 A
Selected soft starter in an inside delta circuit 3RW44 22
Figure 3-4:Name plate of a 22 kW motor
The SIRIUS 3RW44 soft starter can be dimensioned to match the current flowing
in the motor section (58 % of the conductor current) by connecting it in the delta winding of the motor. This requires at least 6 motor lines.
The 3RW44 soft starter automatically detects how it is connected so the connection type does not have to be explicitly set on the device. The detected connection type can be read on the starter under the menu item "Status display/ Connection type". In this case the display reads "Inside delta circuit". If the circuitry is faulty or the motor is not connected, the display shows "Unknown".
Protection of the Soft Starter against Short Circuits
The soft starter has integrated thyristor protection against overloading. In the event of a short circuit, e.g. due to a defect in the windings of the motor or auto short-circuit via the motor supply cables, this internal thyristor protection function is not sufficient. Special semiconductor fuses, e.g. SITOR fuses from SIEMENS, must be used for this purpose.
Installation Altitude and Ambient Temperature
The permissible installation altitude must not exceed 5,000 m above sea level (above 5,000 m on request)
If the installation altitude exceeds 1,000 m, the rated operating current must be reduced for thermal reasons.
If the installation altitude exceeds 2,000 m, the rated voltage must also be reduced because of the limited insulation strength. For installation altitudes between 2,000 m and 5,000 m above sea level, only rated voltages ≤460 V are allowed.
The following illustration shows the reduction in the rated device current in relation to the installation altitude: The rated operating current Ie must be reduced when installed at 1,000 m above sea level or higher.
Ambient temperature
The 3RW44 soft starters are designed to be operated with a nominal current at an ambient temperature of 40 ° Celsius. If this temperature is exceeded, e.g. due to excessive heating up in the switchgear cabinet, other loads or due to a higher general ambient temperature, this will influence the performance of the soft starter and must be taken into account in the dimensioning process
If the installation altitude exceeds 1,000 m, the rated operating current must be reduced for thermal reasons.
If the installation altitude exceeds 2,000 m, the rated voltage must also be reduced because of the limited insulation strength. For installation altitudes between 2,000 m and 5,000 m above sea level, only rated voltages ≤460 V are allowed.
The following illustration shows the reduction in the rated device current in relation to the installation altitude: The rated operating current Ie must be reduced when installed at 1,000 m above sea level or higher.
Ambient temperature
The 3RW44 soft starters are designed to be operated with a nominal current at an ambient temperature of 40 ° Celsius. If this temperature is exceeded, e.g. due to excessive heating up in the switchgear cabinet, other loads or due to a higher general ambient temperature, this will influence the performance of the soft starter and must be taken into account in the dimensioning process
On-time and Switching Frequency
In terms of motor rated current and normal/heavy starting, the 3RW44 soft starters are dimensioned for a maximum permissible switching frequency in combination with a relative on-time. "Technical Data Power Unit". If these values are exceeded, you may have to select a larger soft starter.
On-time OT
The relative on-time OT in % corresponds to the relationship between the load duration and the switching-cycle period of loads that are frequently switched on and off.
The on-time OT can be calculated using the following formula:
On-time OT
The relative on-time OT in % corresponds to the relationship between the load duration and the switching-cycle period of loads that are frequently switched on and off.
The on-time OT can be calculated using the following formula:
Normal or Heavy Starting
To properly dimension a soft starter, it is important to know and take into account the starting time (normal or heavy starting) of the application. Long starting times mean a higher thermal load for the thyristors of the soft starter. The 3RW44 soft starters are designed for continuous operation under normal starting conditions
(CLASS 10), an ambient temperature of 40 degrees Celsius and a fixed switching frequency. You can also find these values in Chapter 10.3.2 "Technical Data Power Unit". If deviations from these data occur, it may be necessary to over dimension the soft starter. Using the Win Soft Starter selection and simulation program from SIEMENS, you can enter your application data and requirements, and it will determine the optimum soft starter dimensions for your application
Selection criteria
The adequate size of the SIRIUS 3RW44 soft starters must be selected on the basis of the motor rated current (Rated current soft starter ≥motor rated current).
(CLASS 10), an ambient temperature of 40 degrees Celsius and a fixed switching frequency. You can also find these values in Chapter 10.3.2 "Technical Data Power Unit". If deviations from these data occur, it may be necessary to over dimension the soft starter. Using the Win Soft Starter selection and simulation program from SIEMENS, you can enter your application data and requirements, and it will determine the optimum soft starter dimensions for your application
Selection criteria
The adequate size of the SIRIUS 3RW44 soft starters must be selected on the basis of the motor rated current (Rated current soft starter ≥motor rated current).
Subscribe to:
Posts (Atom)